Operation Manual
12
EG
ERROR
LEDS
OPERATION TIMER STANDBY
POSSIBLE CAUSE SYSTEM BEHAVIOUR SOLUTION
E3
F F F
Communication error between the 
outdoor unit and the indoor unit
Fan is stopped and flap is closed 
after 30 seconds of missing 
communication.
The system restarts automatically 
as soon as the communication is 
recovered.
Check that connections between C1 
and C2 on outdoor and indoor terminal 
block are correct (C1 terminals 
connected together, C2 terminals 
connected together).
Check that a shielded communication 
cable has been used.
Check that the dip-switch SW2 for 
communication address setting is in 
the correct position.
Check that all earth cables are 
properly connected to every terminal.
Check that the shield of the 
communication cable is properly 
connected to every terminal.
Check the communication fuse on 
outdoor and indoor unit.
Check that the outdoor unit has power 
supply and that it is working.
Check that all PCBs are powered on.
Be sure that power supply has not 
been connected to the communication 
terminals.
Check that there are no burnt signs 
on the PCBs, in particular close to 
communication cables.
Check that the fan motor is not 
damaged and it doesn’t create short 
circuit on the indoor PCB.
O = LED OFF 
l  
= LED ON  F = Flashing LED










