To configure the temperature alarm:
1. If you have a GV-System subscriber, make sure the Send temperature status to Vital
Sign Monitor option is enabled. For details, see 5.3.2 Notification messages on System
Status.
2. On the VSM window, click Configure and select Temperature Monitor. The
Temperature Monitor dialog box appears.
3. In the Units section, select Celsius or Fahrenheit. The selected unit will be used in the
alarm message.
Figure 5-6
4. To show both units in the Subscriber Status (Figure 5-5), select Show both units.
Tip: With the Show both units option is selected, select either Celsius or Fahrenheit for
the unit to come before the other in the Subscriber Status.
5. In the Alarm section, specify the critical temperature.
6. Click OK. Once the temperature reaches or exceeds the critical temperature, an alarm
event will be shown on the VSM window.