Technical data
Electronic scale eliminator ANTICA
++
3
treatment and is rendered useless. However the installation of the device in open water
circuits downstream of the reservoir or holding tank is beneficial.
In closed water circuits the installation of the device upstream of the holding tank is highly
recommended. When the device is installed upstream of the holding tank, then the tank doubles
as a sedimentation vessel where the scale separates from the water. The sediments can then be
flushed out of the system. However, if thus treated water is not used within 48 hours the
treated water reverts to the raw supplied water state and needs to pass again through AntiCa++
device to protect the system.
If in doubt of the device placement in the systems consult with the manufacturer or his
representative.
Basic requirements:
Before installing the device on the designated pipe, determine the hardness of the raw water
in pH. Where possible determine the amount of iron (Fe) in the raw water. From the water
hardness analysis consult Table 1 below and install the number of coil windings indicated. If the
water hardness is greater than 40°dH, then it is necessary to order a special device.
For devices EUV xx Dom, D and T wind the number of coil windings as indicated in Table 1
Total water
hardness °dH
<16 16 - 24 24 - 32 32 - 40 > 40
Number of coil
windings (2x)
11 12 13 14 15
In case the water hardness cannot be determined then it is recommended to install 2 x14 coil
windings.
For devices EUV xx MI, TI and AI wind 2x11 coil windings with the separation distance
between coils shown in Table 2 below in metric
DN of piping [mm] 50 - 65 80 - 100
125 - 150
200 - 250
300 - 500
Distance L [mm] 200 250 300 500 800
For devices EUV xx MI, TI and AI wind 2x11 coils windings with the separation distance
between coils shown in Table 2 below in imperial units
DIA of piping [in] 2 – 2
1
/
2
3 - 4 5 - 6 8 - 10 12 - 20
Distance L [in] 8 10 12 20 32
For devices EUV xx MI and TI set up the strength of signal:
• in accordance with the table printed on the side panel of the device for water hardness up
to 20°dH
• one step up for water hardness between 20 - 30°dH ( eg. from 7 to 8 )
• two steps up for water hardness between 30 - 40°dH ( eg. from 6 to 8 )
• for water hardness above 40°dH it is necessary to consult on the settings with the
manufacturer or his representative and/or order a special device
Note:
• When the water analysis reveals that the iron (Fe) content is Fe>1 mg/l and pH <6.5 or >8.3
it is necessary to consult on the device settings with the manufacturer or his representative.
Installation:
1. Fasten the device to the wall with the supplied screws at a distance of 1,5 m max from the
installed coils on the pipe that is intended for protection.
• For devices EUV xx MI, TI and AI screw in the plastic hanging eyes supplied.
• For devices EUV xx T and TI install and connect the timer (when timer is part of the supply).