ANTICA++ Electronic scale eliminator Application of AntiCa++ devices AntiCa++ devices are intended to protect: • Boilers and heat generators • Home appliances and domestic hot water heaters, including gas-fired instant hot water systems, eliminating expensive maintenance of heating elements • Heat exchangers, converters, water distribution systems, heating district distribution systems, generation of hot water, hydronic systems • Process equipment and systems in which the formation of scale takes place as
ANTICA++ Electronic scale eliminator treatment and is rendered useless. However the installation of the device in open water circuits downstream of the reservoir or holding tank is beneficial. In closed water circuits the installation of the device upstream of the holding tank is highly recommended. When the device is installed upstream of the holding tank, then the tank doubles as a sedimentation vessel where the scale separates from the water. The sediments can then be flushed out of the system.
ANTICA++ Electronic scale eliminator • For devices EUV xx AI connect to water volume measuring device. 2. From supplied power cable (red), wind on vertical or horizontal straight pipe 2 coils with the number of turns indicated in Table 1 and the distance between them indicated in Table 2. Please note that both windings must run in the same direction as shown on the installation diagrams for each type of the device.
ANTICA++ Electronic scale eliminator Considerable effort should be made to monitor the system where the AntiCa++ device is installed. On older systems where scaling took place before the AntiCa++ device installation, the treated water softens the scaling and in time may restore the system to its original state. Depending on the severity of system scaling, the loose scale in piping systems with reduced flow velocity can settle in any place and invoke system blockage.
ANTICA++ Electronic scale eliminator Technical data of EUV xx Dom devices. Water Flow Type EUV 15 EUV 20 EUV 25 EUV 32 EUV 40 EUV 50 EUV 65 Dom Dom Dom Dom Dom Dom Dom 3 [m /hour ] 0.1 0.2 0.3 0.4 0.8 1.2 2.0 – - 0.3 0.6 0.9 1.4 2.3 3.5 6.0 [USGPM] 1.6 – 4.75 3.17-9.51 4.75-14.26 6.34-22.19 12.68-36.45 19-55.47 31.7-95.1 Max.
ANTICA++ Electronic scale eliminator Technical data of EUV xx D. Water Flow Type EUV EUV EUV EUV EUV EUV EUV EUV 10 15 20 25 32 40 50 65 3 D D D D D D D D [m /hour ] [USGPM] 0.1 - 0.45 0.3 - 1 0.6 - 1.8 0.9 - 2.7 1.4 - 4.4 2.3 - 6.8 3.5 -10.5 6.0 -18.0 1.6 - 4.75 4.75 -15.85 9.51-28.53 14.26-42.79 22.19-69.74 36.45-107.78 55.47-166.42 95.1-285.3 Max.
ANTICA++ Electronic scale eliminator Techical data of EUV xx T. Water flow Type [m3/hour ] I. 0,.4 -1.4 II. 1.4 -4.4 I. 0.8 –2.3 EUV 40 T II. 2.3 -6.8 I. 1.2 –3.5 EUV 50 T II. 3.5 10.5 I. 2.2 – 6.0 EUV 32 T EUV 65 T II. 6.0 18 [USGAL] 15.85 - 22.19 22.19 - 69.74 12.68 – 36.45 36.45 -107.78 19 – 55.47 55.47 -166.42 Max. pipe diameter Internal Ext.
ANTICA++ Electronic scale eliminator Technical dada of EUV xx MI, TI and AI. Water Flow Type MI, TI, AI 3 [m /hr] EUV 50 0.2–11 EUV 65 0.3–18 EUV 80 0.5–27 EUV 100 0.8–42 EUV 125 1.4–66 EUV 150 2.0-100 EUV 200 3.2-170 EUV 250 6.0-270 EUV 300 8.0-380 EUV 400 1.0-680 EUV 500 2.0-1100 [USGPM] 3.17 -174.35 4.75 -285.3 7.92 -427.95 12.68 – 665.7 22.19 -1046.1 31.7 -1585 50.72 -2694.5 95.1 -4279.5 126.8 -6023 15.85 -10778 31.7 -17435 Max. pipe diameter Internal Ext.
ANTICA++ Electronic scale eliminator Installation of EUV xx TI. L – distance between coil windings ( see. page.4) Installation of EUV xx AI. L – distance between coil windings (see. page.
ANTICA++ Electronic scale eliminator Timer TM-6331 (Daily and weekly programming). Button functions: CLOCK Indication and time setting DAY Day setting HOUR Clock setting MIN Minutes setting TIMER Selection of individual time duration On/Off MANUAL Manual operation On/Off R Accepts all settings and starts the program Installation: Take out the screw located on front panel in right corner. The plate with terminals is located there. Affix the plate and connect wires in accordance with schematic.
ANTICA++ Electronic scale eliminator Specifications of timers model TM 6331. Power Max. current Back-up 120VACV ,50 – 60 Hz 16 A / 250 V alternate. Cosφ=1 20 A / 125 V alternate. Cosφ=1 Battery CR2032 Ambient temperatures -10 to + 50°C non-corrosive atmosphere Number of contacts Programming Accuracy Time 16 (8 NO and 8 NC) 8 timers with 15 modes ± 0,5 sec.
ANTICA++ Electronic scale eliminator Technical data for digital Volume measurement devices EUV xx AI. (OPTO OD 01, OD 02.) Sensor Specification Constant IR – reflection ray in accordance with DIN 19234 8,2 V DC ( z EUV xx Feeder voltage AI ) Reflection currant < 1 ,2 mA Current without reflection > 2,1 mA DN 40 - 125 1 impulse / litre DN 150 - 300 1 impulse / 10 litres Connecting digital volume counting sensor: 1. Connect middle wire (opto+) shield cable to terminal #4. 2.
ANTICA++ Electronic scale eliminator Technical data of AntiCa++ devices Power Room temperature Pipe surface temperature EUV xx Dom Other types Length of power coil cable (red) Length of power cord EUV xx Dom Other types Weight EUV EUV 15 - 25 Dom EUV 32 - 65 Dom EUV 15 - 80 D EUV 32 – 65 T EUV xx MI, TI AI Input EUV EUV 15 - 50 Dom EUV 65 - 65 Dom EUV 10 – 50 D EUV 65 - 80 D EUV 32 T – 65 T EUV 50 – 100 MI, TI, AI EUV 125 – 300 MI, TI, AI EUV 400 – 500 MI, TI, AI Contact signal functions Load on contact r