This parameter contains a list of signals available for selection
in par. 9-15 and 9-16.
9-27 Parameter Edit
Option: Function:
Parameters can be edited via Profibus, the standard RS485 in-
terface, or the LCP.
[0] Disabled Disables editing via Profibus.
[1]
*
Enabled Enables editing via Profibus.
9-28 Process Control
Option: Function:
Process control (setting of Control Word, speed reference, and
process data) is possible via either Profibus or standard fieldbus
but not both simultaneously. Local control is always possible via
the LCP. Control via process control is possible via either termi-
nals or fieldbus depending on the settings in par. 8-50 to 8-56.
[0] Disable Disables process control via Profibus, and enables process con-
trol via standard fieldbus or Profibus Master class 2.
[1]
*
Enable cyclic master Enables process control via Profibus Master Class 1, and disables
process control via standard fieldbus or Profibus Master class 2.
9-44 Fault Message Counter
Range: Function:
0
*
[0 - 8] Indicates the number of fault events presently stored in par.
9-45. The buffer capacity is maximum eight error events.
The buffer and counter is set to 0 by reset or power-up.
9-45 Fault Code
Option: Function:
Array 64 This buffer contains the alarm-word for all alarms and warnings
that have occurred since last reset or power-up.
The buffer capacity is maximum eight error events.
9-52 Fault Situation Counter
Range: Function:
0
*
[0 - 1000] Indicates the number of fault events occurred since last reset
or power-up.
9-53 Profibus Warning Word
Option: Function:
This parameter displays Profibus communication warnings.
Please refer to the
Profibus Operating Instructions
for further
information.