Operating instructions
IMPORTANT NOTES
IMPORTANT NOTES
A properly sized pressure tank of either style will require a minimum pump cycle of 60 seconds to refi ll from the well pump on-to-off
pressure settings. If cycle time of pump is less than 60 seconds, pressure tank is too small, causing excessive wear on the pump
and probable failure of the fi lter system.
Under more severe operating conditions (low pH, high iron, manganese and small concentrations of sulfur), a standard air-to-water
type pressure tank with an air-relief valve MUST be used (if bladder type tank is already in place, do not remove it. Install the air-to-
water pressure tank between the Hydro-Charger and the bladder type-tank).
IMPORTANT NOTE
IMPORTANT NOTE
If your pressure tank (or any part of your water system) is not functioning properly, corrective action MUST be taken BEFORE
installation of your Chem-Free Iron Reduction Filter.
Facts To Remember While Planning Your Installation:
WARNING
WARNING
To reduce the risk associated with hazardous voltage:
• If the home electrical system requires use of the cold water system as an electrical safety ground, a jumper must be used to
ensure a suffi cient ground connection across the fi lter installation piping — refer installation to qualifi ed personnel.
CAUTION
CAUTION
To reduce the risk associated with property damage due to water leakage:
• Installation must comply with existing state or local plumbing codes.
• Do not install if water pressure exceeds 100 psi (689 kPa). If the system water pressure exceeds 100 psi, the installation
must use a pressure limiting valve. Contact a licensed plumbing professional if you are uncertain how to check your water
pressure.
• Do not install system where water lines could be subjected to vacuum conditions without appropriate measures for vacuum
prevention.
• Do not use torches or other heat sources near plastic plumbing, as damage may occur.
• Take care when using pliers or pipe wrenches to tighten plastic fi ttings, as damage may occur.
• On plastic fi ttings, use thread sealing tape only. Never use pipe sealant or pipe dope on plastic fi ttings, as damage may occur.
To reduce the risk associated with property damage due to plugged water lines:
• Pay particular attention to correct orientation of control valve. Water fl ow should match arrow on control valve. The Inlet and
Outlet of other water treatment equipment products will vary depending on the control valve brand used.
All water to be treated MUST pass through the Hydro-Charger Assembly, pressure tank and the Chem-Free Filter. Refer to the special
instructions for a split-stream installation. System may malfunction if this instruction is ignored.
If lawn sprinkling, a swimming pool, geothermal heating/cooling or water for other devices/activities are to be treated by the Chem-
Free Iron Reduction fi lter, a larger model fi lter MUST be selected to accommodate the higher demands of these items. The pumping
rate of the well pump must be suffi cient to accommodate these items plus the backwashing requirement of the fi lter. Consult your
dealer for alternative instructions if the pumping rate is insuffi cient.
Remember that the fi lter INLET is attached to the pipe that supplies water (i.e. runs to the pump) and OUTLET is the line that runs
toward the water heater or other water treatment equipment device.
Before commencing the installation, it is advisable to study the existing piping system and to determine the size, number and type of
fi ttings required. Typical system schematics shown in Figure 1 will be of assistance.
2-4