DO NOT use an open flame to check for leaks. Check all gas piping for leaks with a soap and water solu-
tion before operating unit.
CAUTION
!
GENERAL INSTALLATION INSTRUCTIONS
Ensure gas supply and gas type, as shown on unit nameplate agree.
Unit installation must conform with the National Fuel Gas Code, ANSI Z223.1-1996, the National Gas In-
stallation Code, CAN/CGA-B149.1, or the Propane Installation Code, CAN/CGA-B149.2 as applicable and
in accordance with local codes.
Screw legs into the permanently fastened nuts on the four corners of the unit and tighten by hand. Level
the unit by turning the adjustment screw at the bottom of each leg. Do not slide unit with legs mounted, lift
if necessary to move unit.
Pipe gas supply to unit.
Pipe threading compound must be resistant to the action of liquefied petroleum gases.
These units are suitable for installation on noncombustible surfaces only.
Noncombustible clearances:
0” sides (0 mm) 6” rear (152 mm)
EUROPEAN COMMUNITY INSTALLATION INSTRUCTIONS:
“THIS APPLIANCE MUST BE FITTED BY A COMPETENT PERSON. IN THE U.K., CORGI REGISTERED
INSTALLERS (INCLUDING THE REGIONS OF BRITISH GAS) UNDERTAKE TO WORK TO SAFE AND
SATISFACTORY STANDARDS. THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH THE
GAS SAFETY (INSTALLATION AND USE) REGULATIONS AND THE RELEVANT BUILDING REGULA-
TIONS / I.E.E. REGULATIONS. DETAILED RECOMMENDATIONS ARE CONTAINED IN THE FOLLOW-
ING BRITISH STANDARD CODES OF PRACTICE - BS 6172, BS 5440 PART 2, BS 6891”
“THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH THE RULES IN FORCE”
“MUST BE INSTALLED IN A WELL VENTILATED AREA. Ventilation requirements ie. B.S. 5440.”
Do not obstruct the flow of combustion and ventilation air, under the unit by the legs or behind the unit by
the flue.
Adequate clearance for air openings into the combustion chamber is required. Do not place objects be-
tween the bottom of the unit and the counter top.
There must be adequate clearance for removal of the front panel. All major parts except the burners are
removable thru the front if the gas line is disconnected.
CANADIAN INSTALLATION MUST COMPLY WITH THE CANADIAN ELECTRICAL CODE, CSA C22.2,
AS APPLICABLE.
The unit, when installed, must be electrically grounded in accordance with local codes or, in the absence of
local codes, with the national electrical code, ANSI/NFPA 70, latest edition.
NOTICE
!
Local codes regarding installation vary greatly from one area to another. The National Fire Protection
Association, Inc. states in its NFPA 96 latest edition that local codes are "authority having jurisdiction" when
it comes to requirements for installation of equipment. Therefore, installations should comply with all Local
codes.
NOTICE
!