8.Technical Data
. Be sure to verify the voltage and current specifications of your PV module match
with those of the Microinverter. Please refer to the datasheet or usermanual
which can be download from APsystems website www.APsystems.com.
. You must match the DC operating voltage range of the PV module with the
allowable input voltage range of the APsystems Microinverter.
. The maximum open circuit voltage of the PV module must not exceed the
specified maximum input voltage of the APsystems
Grid Support Details
The QS1 is a grid support interactive inverter. This type of inverter is also known as a Grid
Support Utility Interactive Inverter . The QS1 also comply with California Rule 21. The grid
support function is controlled by ECU .
Simultaneous use of Fixed Power Factor and Volt/VAr is not supported.
Manufacturer
s Stated Accuracy
Measurement
Default Tolerance of Measurement
Volts
2V
VAr
10%
power factor
0.05
Hz
+/-0.1Hz
SA9: Low/High Voltage Ride Through (L/H VRT) and Must Trip Settings
Region
Voltage(%Nomin
al Voltage
Ride-Through
Until (s)
Operating Mode
Maximum Trip
Time (S)
High voltage 2 (HV2
High voltage 1 (HV1
Near Nominal (NN)
Low voltage 1 (LV1)
Low voltage 2 (LV2)
Low voltage 3 (LV3)
V 120
110 < V <120
88 V 110
70 V 88
50 V 70
V < 50
Not Applicable
12s
Indefinite
20s
10s
1s
Not Applicable
Momentary Cessation
Continuous Operation
Mandatory Operation
Mandatory Operation
Momentary Cessation
0.16s
13s
Not Applicable
21s
11s
1.5s