Product Manual

QS1 Installation/User Manual
19
8.1 QS1 Microinverter Datasheet
Note 1: Utility Interconnection Voltage and Frequency Trip Limits and Trip Times
Voltage and frequency limits for utility Interaction
Condition
Simulated utility source
Maximum time (sec)
(cycles) at 60 Hza
before cessation of
current to the
simulated utility
Trip time accuracy
Voltage (V)
Frequency (Hz)
A
< 0.50 Vnor
Rated
160ms
+/-80ms
B
0.50 Vnor V < 0.88 Vnor
Rated
1000ms
+/-200ms
C
1.10 Vnor < V < 1.20 Vnor
Rated
1000ms
+/-200ms
D
1.20 Vnor V
Rated
160ms
+/-80ms
E
Rated
f > 60.5
160ms
+/-200ms
F
Rated
f < 59.3
160ms
+/-200ms
© All Rights Reserved
Specifications subject to change without notice - please ensure you are using the most recent update found at www.APsystems.com
*APsystems online Energy Management Analysis (EMA) platform
2018/7/3 Rev1.1