RSD-D Installation & User Manual
User Manual
15
TECHNICAL DATA
—
TRANSMITTER-PLC-OUTDOOR KIT
Model
Main electrical data
Transmitter-PLC-Outdoor Kit
Main electrical data
Input Voltage
12VDC
Input Current
0.8A
Communication
PLC
Power Supply
Residential(optional)
85-264VAC Input, 12VDC Output, 90 mm x 17.5 mm x 58.4 mm
Commercial
(
optional
)
180-550VAC Input, 12VDC Output, 125.2 mm x 32 mm x 102 mm
Core data
29mm Core
Max.Current
150A Per core
150A Per core
Max. System Voltage
1500VDC
1500VDC
Internal Opening for Wires/Outside Dimensions
~29mm/65mm
Max. Supported PV Modules per String
30 modules
30 modules
30 modules
Number Of Strings Per Core
DC Cable Diameter(without connector)
Φ5.9mm
Φ6.35mm
Φ7mm
Φ8.6mm
29mm Core
≤15
≤15
≤14
≤10
Environmental
Temperature
-40℃
~
+60℃
Structure data
Dimensions (W x H x D)
198.5 mm x 298 mm x 179 mm
Enclosure Environmental Rating
IP30
Features & Compliance
Safety Compliance
NEC 2017 & 2020 (690.12); UL1741; CSA C22.2 No. 330-17
EMC Compliance
FCC Part15; ICES-003
600 Ericksen Ave NE, Suite 200 Seattle, WA 98110 | +1-737-218-8486 |
+1-866-374-8538 | support@APsmartGlobal.com | APsmartGlobal.com