Install Instructions
VENT-AUTO & VENT-TIMED
The dehumidifier can ventilate in four modes.
Vent-Timed: Ventilation occurs based only on time setting; no temperature restrictions�
Vent-Auto-B: Ventilation prevented when outdoor temperature is below 0°F and above 100°F� Between 0°F – 20°F ventilation is only allowed during
a HVAC heat call�
Vent-Auto-C: Ventilation prevented when outdoor temperature is below 0°F and above 100°F�
Vent-Auto-D: Ventilation prevented when outdoor temperature is below 0°F and above 90°F� Between 0°F – 40°F ventilation is only allowed during
a HVAC heat call�
Vent-Auto-B, -C, -D modes apply outdoor temperature limits and require an outdoor temperature sensor to be installed�
OUTDOOR TEMPERATURE SENSOR INSTALLATION
The Outdoor Temperature Sensor should be installed outside in a shaded location, or in the outdoor air intake duct�
NORTH, EAST
OR WEST SIDE
OF HOME
OUTDOOR
TEMPERATURE
SENSOR
SENSOR
SENSOR
BRACKET
ABOVE EXPECTED
SNOW LINE
OUTDOOR
TEMPERATURE SENSOR
LEADS
36" MAX.
CENTER LINE
OUTSIDE WALL
B2202617-D B2202617-E
FIGURE 25 – ODT MOUNTED OUTSIDE FIGURE 26 – ODT MOUNTED IN INTAKE DUCT
20 English