Installation Manual

TABLE 1 – DIAGNOSTIC CODES
Diagnostic
Code Failure Mode Action Reset
E7 Float Switch Open
1. Empty the condensate pan�
2. Check the float switch connection at the control board�
3. If not using a float switch, verify jumper is between float switch terminals on dehumidifier control
board�
4. If the problem persists, replace the float switch�
Self-Correcting
E8
Inlet Air
Temperature Out of
50°F – 104°F range,
or dew point below
40°F
1. If temperature is out of range, no action, normal operation�
2. If air temperature is between 50°F – 104°F with a dewpoint above 40°F, contact Technical Support�
Self-Correcting
TABLE 2 – TROUBLESHOOTING GUIDE
Symptom Possible Reason Troubleshooting Procedure
Dehumidifier does not
turn on/run�
No power to unit�
Check that the dehumidifier is plugged in�
Check that the power switch is turned ON�
Check that the control is turned ON�
Check that the circuit breaker has not tripped�
Dehumidifier blower is
running but with little or
no airflow
Pressure drop across dehumidifier
is higher than 0�6" w�c�
Check dehumidifier air filter and wash or replace�
Check for blocked duct work and clear�
Verify that the outlet collar with backflow damper is installed on the outlet side of the
dehumidifier
Check if backflow damper is blocked or stuck and remove obstruction
Dehumidifier blower is
running but compressor
is not�
Float switch open�
If float switch installed, check connections at control board and empty condensate pan�
If no float switch installed check that the jumper is installed at the float switch terminals on
the control board�
Coil frosting�
Lack of or reduced airflow� Check dehumidifier air filter and wash or replace�
Check that there is nothing blocking the inlet or outlet of the dehumidifier
Inlet air conditions below 60°F� Increase the humidity setting�
Inlet air temperature is outside of
the 50°F – 104°F range or the dew
point is below 40°F and there is a
demand for dehumidification�
Verify all ductwork is properly sealed�
No action� The compressor will not run if inlet conditions are out of range
Dehumidifier is not
draining properly
Drain line blocked or unit not level�
Verify that the unit is level�
Check the drain line blockages and for a continuous downward slope�
Verify presence and condition of drain cover� Clean following procedure under Maintenance
or replace with part number 5885 if missing or damaged�
Dehumidifier is
producing hot air
Normal function�
Air is reheated across the condenser coil, resulting in a temperature rise between inlet and
outlet�
The HVAC fan turns on
unexpectedly
Dehumidifier is sampling�
The dehumidifier will turn on the HVAC fan during air sampling or as needed to meet the
ventilation time�
14 English