Install Instructions

START-UP
1. Press the ON/OFF button to turn the dehumidifier control ON. The
display will show the current dew point or %RH setting, and the
dehumidifier blower will turn on to start sampling the air.
“AIR SAMPLING” will show on the display.
2. Use the UP or DOWN button to adjust the dew point setting or
%RH setting as desired. The recommended initial setting is 3
using dew point control or 59%RH, for preservation and preventing
condensation on floor joists. See Table 1.
3. After three (3) minutes of sampling, the measured dew point or
%RH will be compared to the setting:
a. If the dew point is above the setting or above the %RH setting,
the dehumidifier compressor turns on and “AIR SAMPLING” will
be replaced by “DEHUMIDIFYING”. The compressor remains
on until the measured dew point falls below the setting or
measured %RH falls 3% below the setting.
b. If the dew point or %RH is below the setting, the blowers turn
off and the display returns to showing the setting.
4. The dehumidifier will sample again every 60 minutes, or at any
time if the humidity setting is lowered.
NOTE: For Start-Up when using a Model 76 Control, reference the
Model 76 Installation Instructions.
TABLE 1 – %RH (+/- 5%) Based on Dryness Setting and
Crawl Space Temperature
Dryness Setting
& Dew Point
Crawl Space Temperature
60°F 65°F 70°F
1 – Less, 65°F DP 84%
2 – 61°F DP 87% 73%
3 – Normal, 57°F DP 90% 75% 63%
4 – Normal, 53°F DP 78% 65% 55%
5 – Normal, 49°F DP 67% 56% 47%
6 – 46°F DP 60% 50% 42%
7 – Most Dry, 42°F DP 51% 43% 36%
EXAMPLE: At a crawl space temperature of 70°F and a dryness level
setting of 3 (57°F DP), the dehumidifier will work to achieve a 63%
relative humidity level.
The %RH values are +/- 5% and are to be used as a GUIDE ONLY.
The crawl space temperature is measured at the dehumidifier inlet.
Your dehumidifier is equipped with two features that protect against unwanted energy consumption. Defrost is a normal operating mode that
helps to prevent significant ice formation on the refrigeration system coil. The dehumidifier display will show “DEFROSTING” when operating
in this mode. This mode can occur when there is not enough air moving through the dehumidifier or if the temperature and/or humidity of
the incoming air is too low. The second protection feature is the E8 code. E8 on the dehumidifier display indicates that the air entering the
dehumidifier is below 50°F or above 104°F, or the dew point of the incoming air is below 40°F. There would be a significant reduction in
dehumidifier efficiency if the dehumidifier operated outside of these conditions. Low dew point conditions can be seen in some basements
or crawl spaces and usually occur in the Winter and Spring months. The dehumidifier continues to monitor the incoming air and when the
conditions are within the operating range, E8 will be removed from the display and dehumidification will begin as needed.
90-1854
Press and hold the ON/OFF button
and MODE buttons for 3 seconds.
The measured humidity, AIR
SAMPLING and TEST will show
on the display. The ALERT LIGHT
will turn on and stay on until the
system check is “DONE”.
90-1854
After three (3) minutes the
dehumidifier compressor will
turn on and DEHUMIDIFYING will
replace AIR SAMPLING on the
control screen.
90-1854
90-1854
After one minute of compressor
operation, all outputs will turn off
and DONE will blink for 3 seconds
and then return to the OFF screen.
SYSTEM CHECK