User Manual
0.38" MIN
2.00" MAX
3/4” DRAIN
FLOAT
Switch
DH DH
NORMALLY CLOSED
FLOAT SWITCH
DRAIN INSTALLATION
LEVELING
CONDENSATE PAN, CONDENSATE PUMP AND FLOAT SWITCH
The feet can be adjusted to level the unit, and
if required, to accommodate drain fittings and a
secondary condensate pan. Leveling is required
to ensure proper drainage from the dehumidifier.
See Figure 9.
The drain outlet on the dehumidifier can be hard piped using a 3/4” PVC Slip x 3/4” MNPT fitting and 3/4” nominal drain tubing or the provided
3/4” MNPT x 3/4” hose barb fitting and 3/4” clear PVC tubing can be used to drain the dehumidifier. Always maintain a constant downward
slope from the dehumidifier to the drain and do not allow soft tubing to curl up which may result in air lock. NOTE: PTFE thread seal tape is
recommended for the threaded connection and hand tighten only. If hard pipe is used, PVC primer and cement is recommended for the slip fit
connection.
Always install the dehumidifier in a condensate pan
when locating in or above a finished space. Adhere
to local codes regarding draining of the condensate
pan. If a condensate pump is needed, install it in the
condensate pan as well.
Install a condensate overflow safety switch (i.e. float
switch) in the condensate pan, remove the factory
installed jumper wire between the Float Switch
terminals on the control and wire the float switch to
the dehumidifier as shown in Figure 10. Overflow
safety switches on condensate pumps can be wired
to the Float Switch terminals in a similar fashion.
FIGURE 9 – Level the Unit
FIGURE 10 – Float Switch Wiring
90-1885
90-1857
9