Installation Guide

21 English
Table 2: Troubleshooting Guide (Continued)
Symptom Possible Reason Troubleshooting Procedure
The ventilation
damper does
not open when
the HVAC fan is
active.
Cycle time has
been met.
The damper will not open if the ventilation time has already been met.
ODT error or
outdoor air
outside of ODT
range.
Check that the ODT is wired correctly
to the dehumidifier control board and
connections are secure.
Check that the ODT is installed in the
outdoor air intake according to the
setup specified in
VENTILATION ON
PAGE 13
.
Remove the ODT leads from the
dehumidifier control board and check
the resistance. Compare the reading
with the chart on the right.
Outdoor
Temperature Resistance
0°F
84,500
Ohms
20°F
46,000
Ohms
40°F
26,000
Ohms
60°F
15,500
Ohms
80°F 9,500 Ohms
100°F 6,000 Ohms
Dehumidifier
is not draining
properly.
Drain line
blocked or unit
not level.
Verify that the unit is level.
Check the drain line blockages and check for a continuous downward
slope.
Verify presence and condition of drain cover insert.
See Maintenance
on page 4
for cleaning procedure, or replace with Part No. 5885 if
missing or damaged.
The HVAC
fan turns on
unexpectedly.
Dehumidifier
is sampling or
ventilation in
progress.
The dehumidifier will turn on the HVAC fan during air sampling or as
needed to meet the ventilation time.
Dehumidifier is
producing hot
air.
Normal function. Air is reheated across the condenser coil, resulting in a temperature
rise between inlet and outlet.