Install Instructions

LEVELING
The feet can be adjusted to level the unit and
accommodate drain fittings and secondary condensate
pans as required� Refer to top mounted bubble level
and adjust feet until bubble is within the outer circle�
Leveling is required to ensure proper drainage from the
dehumidifier� See FIGURE 11
CONDENSATE PAN, CONDENSATE PUMP AND FLOAT SWITCH
Always install the dehumidifier in a condensate pan
when locating in or above a finished space� Adhere
to local codes regarding draining of the condensate
pan� If a condensate pump is needed, install it in the
condensate pan as well�
Install a condensate overflow safety switch (i�e� float
switch) in the condensate pan, remove the factory
installed jumper wire between the Float Switch
terminals on the control and wire the float switch to the
dehumidifier as shown in FIGURE 12� Overflow safety
switches on condensate pumps can be wired to the
Float Switch terminals in a similar fashion�
0.38" MIN
2.00" MAX
3/4" DRAIN
BUBBLE LEVEL
FLOAT
Switch
DH DH
NORMALLY CLOSED
FLOAT SWITCH
DRAIN INSERT
90-2592
90-1857
90-2607
FIGURE 11 – LEVEL THE UNIT
FIGURE 12 – FLOAT SWITCH WIRING
FIGURE 10 – DRAIN INSERT
9