Install Instructions

WIRING INSTRUCTIONS
1. Disconnect electrical service at the main fuse or circuit breaker box�
2. Install any code required disconnects to the line service within
eyesight of the appliance�
3. Remove the side panel and electrical service panel from the
dehumidifier� See FIGURE 7
4. Route the service cable through the 7/8" diameter hole where the
power cord was removed� USE ONLY COPPER SUPPLY WIRES�
5. Secure the cable/conduit to the dehumidifier using fittings/
connectors approved for the type of cable/conduit used�
6. Connect the ground wire of the service cable to the ground lug in
the electrical service box� See FIGURE 8
7. Connect the line voltage wires of the service cable to the LINE BLK
and NTRL WHT terminals� See FIGURE 8
8. Reattach the electrical service panel and side panel�
9. Restore electrical service at the main fuse or circuit breaker box�
SIDE PANEL
ELECTRICAL SERVICE BOX
GROUND LUG
NEUTRAL
GROUNDLINE VOLTAGE
ELECTRICAL
SERVICE BOX
115V AC WIRING
TERMINALS
FITTING AS
REQUIRED
LINE SERVICE
CABLE/CONDUIT
90-2609
90-2609
FIGURE 7 – ELECTRICAL SERVICE BOX LOCATION
FIGURE 8 – HARD WIRE TO 115 VAC SERVICE