Install Instructions
SPECIFICATIONS
MODEL E080 MODEL E100
Unit Weight 63 lbs� 64 lbs�
Shipping Weight 81 lbs� 82 lbs�
Capacity
80°F, 60% RH Conditions
80 pints per day @ 185 CFM 100 pints per day @ 280 CFM
Power
115 VAC, Single Phase, 60Hz
5�1A operating current 6�9A operating current
Dehumidifier Inlet Air Conditions
Dehumidification: 50°F – 104°F, 40°F dew point minimum
Ventilation: 40°F – 140°F, 0%RH – 99%RH (non-condensing)
Filter MERV 8, washable
Airflow
External Static Pressure ("w.c.) Airflow (CFM) External Static Pressure ("w.c.) Airflow (CFM)
0�0 185 0�0 280
0�2 135 0�2 245
0�4* 85 0�4 210
0�6* 175
NOTE: Rated capacity and current draw measured at 80°F/60% RH inlet conditions at 0.0 external static pressure.
*Maximum design external static pressure.
SET UP DEHUMIDIFIER FOR INSTALLATION
IMPORTANT: Cut the strap securing the compressor
shipping support bracket and remove the strap and shipping bracket�
SeeFIGURE1�
CLIP OFF
PLASTIC STRAP
REMOVE SHIPPING BRACKET
90-1908
FIGURE 1 – REMOVE SHIPPING BRACKET
3