Install Instructions
VENT-AUTO & VENT-TIMED
THE DEHUMIDIFIER CAN VENTILATE IN FOUR MODES
VENT-TIMED: Ventilation occurs based only on time setting; no temperature restrictions�
VENT-AUTO-B: Ventilation prevented when outdoor temperature is below 0°F and above 100°F� Between 0°F – 20°F ventilation is only allowed
during a HVAC heat call�
VENT-AUTO-C: Ventilation prevented when outdoor temperature is below 0°F and above 100°F�
VENT-AUTO-D: Ventilation prevented when outdoor temperature is below 0°F and above 90°F� Between 0°F – 40°F ventilation is only allowed
during a HVAC heat call�
VENT-AUTO-B, -C, -D modes apply outdoor temperature limits and require an outdoor temperature sensor to be installed�
OUTDOOR TEMPERATURE SENSOR INSTALLATION
The Outdoor Temperature Sensor should be installed outside in a shaded location, or in the outdoor air intake duct�
NORTH, EAST
OR WEST SIDE
OF HOME
OUTDOOR
TEMPERATURE
SENSOR
SENSOR
SENSOR
BRACKET
ABOVE EXPECTED
SNOW LINE
OUTDOOR
TEMPERATURE SENSOR
LEADS
36" MAX.
CENTER LINE
OUTSIDE WALL
B2202617-D B2202617-E
FIGURE 30 – ODT MOUNTED OUTSIDE FIGURE 31 – ODT MOUNTED IN INTAKE DUCT
20