Install Instructions

SYSTEM SET-UP AND CHECKOUT
If dehumidifier installation does not include ventilation or zoning and
will not be wired to an external control, remote control or the HVAC
system, proceed to INSTALLER TEST MODE section on page 17
1. Check all wiring�
2. Make sure the wire access cover has been snapped back onto the
on-board control�
3. Plug unit in and turn power switch to ON�
4. The on-board control screen should display OFF
90-1854
NOTE: If the display backlight is not on, the first button press (any
button) will only turn on the backlight� Press the button a second time
to achieve function�
5. Hold the MODE button on the on-board control for 3 seconds to
enter the Installer Set-up Menu�
6. Navigate through the following screens to set up the dehumidifier
for the installed application�
7. Use the
or button to select items and use MODE to switch
to the next set-up option� To exit installer set-up, all options must
be scrolled through using the MODE button�
8. After the installer set up options have been completed, DONE will
blink for 3 seconds and the control will return to the OFF screen�
90-1854
90-1854
REMOTE CONTROL – CRAWL SPACE/SEALED ATTIC
90-1854
If not installing in a crawl space or
sealed attic with Model 76 remote
control, press MODE to go to
VENT screen selections
90-1854
If installing in a crawl space or
sealed attic with remote control,
Enable and press MODE� The
installer set-up is complete,
proceed to INSTALLER TEST
MODE section on page 17
VENTILATION
90-1854
If not using the dehumidifier to
bring in outdoor air, press MODE
to go to ZONE screen selections�
90-1854
If using the dehumidifier for
ventilation, enable and press
MODE to select TIMED or AUTO
90-1854
If ventilating based on time
only (no outdoor temperature
restrictions), press MODE at the
VENT TIMED screen to go to
ventilation time selection screen�
If ventilating with outdoor temperature restrictions, use the
button
to go from VENT TIMED to VENT AUTO –B and then the or
button to select the desired ventilation mode, B, C, or D� Press MODE
to go to the ventilation time selection screen�
90-1854
VENT-AUTO-B: Ventilation
prevented when outdoor
temperature is below 0°F and
above 100°F� Between 0°F – 20°F
ventilation is only allowed during
a HVAC heat call�
90-1854
VENT-AUTO-C: Ventilation
prevented when outdoor
temperature is below 0°F and
above 100°F
90-1854
VENT-AUTO-D: Ventilation
prevented when outdoor
temperature is below 0°F and
above 90°F� Between 0°F – 40°F
ventilation is only allowed during
a HVAC heat call�
VENT-AUTO-B, -C, -D modes apply outdoor temperature limits and
require an outdoor temperature sensor to be installed�
90-1854
Press the or button to
adjust the ventilation time per
hour from 0 to 60 minutes� After
selecting time, press MODE to go
to the ZONE screen selections�
15