Install Instructions

DUCTING FOR TWO ZONE INSTALLATIONS
NOTE: Dehumidifier zoning is not recommended in
HVAC zoning applications�
In this installation the dehumidifier controls the
humidity in two separate zones, a Primary and
Secondary Zone� The dehumidifier will dehumidify the
Primary Zone as the first priority, and will switch to the
Secondary Zone after the dehumidification needs of the
Primary Zone have been satisfied�
IMPORTANT: Normally Closed dampers must be
installed in the ducts serving the Primary Zone and
Normally Open dampers installed in the ducts serving
the Secondary Zone.
REQUIRED COMPONENTS
10" ductwork and fittings
Grilles with 10" duct collars
Drain line
2 – Aprilaire Model 6510, 10" Normally Closed damper
2 – Aprilaire Model 6610, 10" Normally Open damper
24 VAC transformer (40 VA min�) for dampers
NOTE: 5442 Basement Kit includes 2 – 6510 Dampers,
2 – 6610 Dampers and a 24 VAC (40VA) transformer
6 ft
MIN
TO/FROM
PRIMARY ZONE
SUPPLY DUCT
RETURN
DUCT
NORMALLY OPEN DAMPER
NORMALLY
OPEN DAMPER
SUPPLY TO
SECONDARY
ZONE
RETURN FROM
SECONDARY
ZONE
NORMALLY
CLOSED
DAMPERS
TO/FROM
SECONDARY ZONE
SUPPLY DUCT
RETURN
DUCT
NORMALLY
CLOSED DAMPER
NORMALLY
CLOSED DAMPER
SUPPLY TO
PRIMARY ZONE
RETURN FROM
PRIMARY ZONE
NORMALLY
OPEN
DAMPER
NORMALLY
OPEN
DAMPER
90-1875
90-1895
FIGURE 20 – WHOLE-HOME PRIMARY ZONE INSTALLATION
FIGURE 21 – WHOLE-HOME SECONDARY ZONE INSTALLATION
12