Product Overview

Fresh Air Ventilator
With Dehumidification
Model 8192A | Specification Sheet
FEATURES
Control Built-in digital control with display
Control mounting option Field interchangeable from top to front
Cabinet insulation 1/2" EPS
Air discharge orientation Top or end air discharge
Inlet/Outlet duct collars 10" round
Back damper at outlet Included
Air filter Washable MERV 8
Refrigeration R-410A
Coil type Corrosion-resistant aluminum
8' Power cord type Plug type
Drain connection
(3)
3/4" PVC
Warranty 5 Years
(3)
Thread adapter and barbed fitting for 3/4” clear drain tubing included.
FEATURES
+ Removes moisture from outdoor air before it enters the living space
+ Unit is designed, when properly installed, to achieve ASHRAE
Standard 62.2
+ Integral moisture and ventilation control
+ Optional ventilation control via thermostat (see below)
+ High and Low Temperature Limit Lock-outs
+ Simple plug-in installation
+ Installation temperature range up to 140°
RECOMMENDED CONTROLS
+ Aprilaire Thermostat Models
-8620, 8620W -8910, 8910W -8920W
+ Aprilaire Communicating Thermostat Models
-8820 -8830 -8840
+ Zone Control Systems
-6010 -6015 -6020 -6025
-6030 -6035 -6040 -6045
BENEFITS
+ Helps control RH in the home during periods when the
air conditioning system does not run long enough to
remove sufficient moisture. If air conditioner can satisfy
RH requirements, the Aprilaire unit’s compressor shuts off
+ Optimize energy savings by locking out ventilation during
hottest/coldest times of the day
+ Improves indoor air quality
+ Installation labor reduced, requires only a power outlet and
24 volt wiring to HVAC system
When properly installed and set, the Aprilaire Model 8192A
ventilator with dehumidification will meet the mechanical
ventilation requirements of:
+ ASHRAE 62.2
+ Energy Star Certified Homes
+ EPA Indoor airPLUS
+ International Residential Code (IRC)
SPECIFICATIONS
Nominal ventilation
airflow (CFM)
200 CFM
Capacity
(1)
pints/day 100 ppd
Energy factor
(1)
2.6 L/kWh
Energy star qualified No
Airflow @ varying E.S.P.
(external static pressure - dry coil)
0.0" w.c.
0.2" w.c.
0.4" w.c.
280 CFM
245 CFM
210 CFM
Voltage, phase, frequency 120VAC, 1, 60 Hz
Current draw
(1)
6.9 Amps
Noise-Fan Only 52.8 dBA (ducted)
Noise-Compressor and Fan 55.0 dBA (ducted)
Dimensions:
Width: 14"
Height: 15"
Length: 26"
Unit Weight
Shipping Weight
64 lbs.
82 lbs.
Inlet air operating conditions during
-Dehumidification:
50°F –104°F, 40°F
dew point min.
-Ventilation: 40°F–140°F, 0%–99% RH
(1)
Rated capacity, energy factor and current draw measured at 80°F/60% RH inlet air at 0.0 ESP.

Summary of content (2 pages)