Installation Manual

0.38" MIN
2.00" MAX
3/4" DRAIN
BUBBLE LEVEL
FLOAT
Switch
DH DH
NORMALLY CLOSED
FLOAT SWITCH
LEVELING
CONDENSATE PAN, CONDENSATE PUMP AND FLOAT SWITCH
The feet can be adjusted to level the unit and
accommodate drain fittings and secondary
condensate pans as required. Refer to top mounted
bubble level and adjust feet until bubble is within the
outer circle. Leveling is required to ensure proper
drainage from the dehumidifier. See Figure 6.
Always install the ventilator in a condensate pan
when locating in or above a finished space. Adhere
to local codes regarding draining of the condensate
pan. If a condensate pump is needed, install it in the
condensate pan as well.
Install a condensate overflow safety switch (i.e. float
switch) in the condensate pan, remove the factory
installed jumper wire between the Float Switch
terminals on the control and wire the float switch to
the ventilator as shown in Figure 7. Overflow safety
switches on condensate pumps can be wired to the
Float Switch terminals in a similar fashion.
FIGURE 6 – Level the Unit
FIGURE 7 – Float Switch Wiring
90-2592
90-1857
English 7