Install Instructions
SPECIFICATIONS
Model 8191 Model 8192
Weight
67 lbs. 75 lbs.
Moisture Removal Capacity
70 pints per day @ 160 CFM
AHAM DH-1-2008 80°F, 60%RH Conditions
95 pints per day @ 265 CFM
AHAM DH-1-2008 80°F, 60%RH Conditions
Power
115 VAC, Single Phase, 60Hz
9A minimum circuit ampacity
6.3A operating current @ 80°F, 60%RH
115 VAC, Single Phase, 60Hz
12A minimum circuit ampacity
8A operating current @ 80°F, 60%RH
Inlet Air Conditions
Ventilation: 40°F – 140°F, 0%RH – 99%RH (non-condensing)
Dehumidification: 50°F – 104°F, 40°F dew point minimum
Filter
MERV 8, washable
TABLE 1A – Model 8191 Ventilation Performance
External Static
(“w.c.) Airflow (CFM) Power (W) Current (A) CFM/watt
CFM/watt
FAN ONLY*
0 160 63 .57 2.54 4.48
0.1 140 63 .56 2.22 3.97
0.2 120 63 .56 1.90 3.55
0.3 100 63 .56 1.59 3.04
0.4 70 62 .56 1.13 2.50
* Unit as just a ventilator (without filtration or dehumidification) provides 245 CFM and uses 69 watts, or 3.55 CFM/watt at 0.2”w.c., meeting the 2012 IECC fan
efficacy requirement.
TABLE 1B – Model 8192 Ventilation Performance
External Static
(“w.c.) Airflow (CFM) Power (W) Current (A) CFM/watt
CFM/watt
FAN ONLY
0 265 153 1.35 1.73 2.84
0.1 245 153 1.34 1.62 2.60
0.2 230 153 1.34 1.50 2.35
0.3 215 153 1.34 1.41 2.13
0.4 200 152 1.33 1.32 1.91
0.5 180 152 1.33 1.19 1.72
0.6 165 151 1.32 1.10 1.50
3