User Guide

LCD INSTALLER SCREEN SETTINGS & DESCRIPTIONS
TABLE 1 – INSTALLER SETUP
Menu Title Description
Factory default setting (bold)
and setting range
EQUIPMENT TYPE Selects if zone panel is controlling a Heat/Cool or Heat Pump system.
HEAT/COOL
HTPUMP
COOLING STAGES Number of cooling stages. Note: Only displayed if EQUIPMENT TYPE is set to HEAT/COOL.
1
2
COMPRESSOR STAGES Number of compressor stages. Note: Only displayed if EQUIPMENT TYPE is set to HTPUMP.
1
2
HEATING STAGES Number of heating stages. Note: Only displayed if EQUIPMENT TYPE is set to HEAT/COOL.
1
2
AUX HEAT STAGES Number of auxiliary heating stages. Note: Only displayed if EQUIPMENT TYPE is set to HTPUMP.
1
2
HEAT EQUIPMENT
Determines if the zone panel or equipment controls the fan in heating. Note: Only displayed if
EQUIPMENT TYPE is set to HEAT/COOL.
GAS
ELECTRIC
AUX HEAT Auxiliary heat type. Note: Only displayed if EQUIPMENT TYPE is set to HTPUMP.
GAS
ELECTRIC
FAN CTL IN PURGE Determines if the fan is controlled by the HVAC equipment or zone panel during purge.
HVAC
ZONE PANEL
PURGE TIME
Selects the number of minutes the fan will run during purge. Note: Only displayed if FAN CTL IN
PURGE is set to ZONE PANEL.
3 minutes
2 to 5 minutes
STAGING BASED ON
Determines if staging of multi-stage equipment is based on the thermostat inputs, the duration
(time) of an active call, or the number of zones that are calling for heating or cooling.
ZONES
TIME
TSTAT
TIME TO STAGE
Number of minutes to delay before engaging second stage Note: Only displayed if STAGING BASED
ON is set to TIME.
10-120 Minutes
(by 10/default 20)
STAGE TIME AUX
Number of minutes to delay before engaging auxiliary heating, or second stage auxiliary heating.
Note: Only displayed if EQUIPMENT TYPE is set to HTPUMP and STAGING BASED ON is set to TIME.
10-120 Minutes
(by 10/default 20)
ZONES TO STAGE
Determines how many zones must be calling for the zone panel to go to the next available stage of
heating or cooling. Note: Only displayed if STAGING BASED ON is set to ZONES.
1-12 (Default 2)
ZONE # WEIGHTING
Determines the weighting of each zone. For example, setting ZONE 2 WEIGHTING to 3 means that
when Zone 2 has an active heating or cooling call, it would count as 3 zones calling for heating or
cooling. Note: Only displayed when STAGING BASED ON is set to ZONES.
1 , 2, 3 (Default 1)
OUTDOOR SENSOR
Determines if an outdoor sensor is installed for balance point control. Note: Only displayed if
EQUIPMENT TYPE is set to HTPUMP.
YES
NO
HIGH BALANCE PNT
Selects the temperature at which the auxiliary heating equipment will be locked out and only the
compressor will be used for heating. Set to Off to disable. Note: Only displayed if EQUIPMENT TYPE
is set to HTPUMP and OUTDOOR SENSOR is set to YES.
OFF 0°F–85°F
(Steps of 5°F/65°F)
LOW BALANCE PNT
Selects the temperature at which the compressor will be locked out and only the auxiliary heat
will be used for heating. Set to Off to disable. Note: Only displayed if EQUIPMENT TYPE is set to
HTPUMP and OUTDOOR SENSOR is set to YES.
OFF 0°F–60°F
(Steps of 5°F/20°F)
DAT SENSOR Determines if a discharge air temperature sensor is installed.
YES
NO
DAT LOW LIMIT
Determines the discharge temperature at which the HVAC equipment will turn off to prevent
freezing the indoor coil. Note: Only displayed if DAT SENSOR is set to YES.
30°F–45°F
(5°F steps/40°F)
DAT HIGH LIMIT
Determines the discharge temperature at which the HVAC equipment will turn off to prevent
overheating. Note: Only displayed if DAT SENSOR is set to YES.
140°F–170°F
(5°F steps/160°F)
DOWN STAGE ON DAT
Allows the zone panel to downstage multistage equipment when DAT temperature come within 5°F
of the DAT LOW LIMIT or DAT HIGH LIMIT. Note: Only displayed if DAT SENSOR is set to YES.
YES
NO
THERMOSTAT TYPE Selects what type of thermostat is being used. Note: All thermostats used must be the same type.
HEAT PUMP
HEAT/COOL
SAVE CHANGES Determines if the previous settings are saved or discarded.
SAVE
DISCARD
English 13