User Guide
INSTALLER SETUP
HOW TO CONFIGURE
• Press the BACK
and NEXT buttons for 7 seconds continuously.
• The message INSTALLER SETUP ENABLED will be displayed for 2
seconds and then transition to the first system setting.
• Use the or arrows to adjust the setting.
• The BACK
button will accept the current setting and navigate to
the previous system setting.
• The NEXT button will accept the current setting and navigate to the
next system setting unless the last system setting is displayed. If the last
system setting is displayed pressing the NEXT button will present the
SAVE CHANGES setting with SAVE selected. Pressing NEXT again
will save any changes that were made by displaying SETUP COMPLETE.
Changing the SAVE CHANGES setting to DISCARD and then pressing
NEXT will exit installer setup without saving any of the changes.
• Note: If no buttons are pressed for 60 seconds during the installer
setup. The installer setup will exit automatically and save any
changes.
The flow chart below shows the steps of the Installer Setup. Default
settings are show in bold. For more detailed information about each of
the system settings, refer to TABLE 1 on the following page.
INSTALLER SETUP
ENABLED
OUTDOOR SENSOR
YES NO
HIGH BALANCE POINT
OFF 0°F–85°F(Steps of 5°F/65°F)
DAT SENSOR
YES NO
DAT LOW LIMIT
30°F–45°F (5°F steps/40°F)
DAT HIGH LIMIT
110°F–170°F (5°F steps/160°F)
DOWNSTAGE ON DAT
YES NO
THERMOSTAT TYPE
HTPUMP HEAT/COOL
SAVE CHANGES
SAVE DISCARD
SETUP COMPLETE
LOW BALANCE POINT
OFF 0°F–60°F (Steps of 5°F/20°F)
(Limited by HBP)
EQUIPMENT TYPE
HTPUMP HEAT/COOL
FAN CTL IN PURGE
HVAC ZONE PANEL
STAGING BASED ON
ZONES TIME TSTAT
ZONES TO STAGE
1-12 (by 1/default 2)
ZONE# WEIGHTING
1 2 3
TIME TO STAGE
10-120 MINUTES
(by 10/default 20)
STAGE TIME AUX
10-120 MINUTES
(by 10/default 20)
PURGE TIME
2 3 4 5
COOLING STAGES
1 2
COMPRESSOR STAGES
1 2
HEATING STAGES
1 2
AUX HEAT STAGES
1 2
HEAT EQUIPMENT
GAS ELECTRIC
AUX HEAT
GAS ELECTRIC
and Held
for 7 Seconds
Return to
Home Screen
HC or HP
HC or HP
ODT Installed
DAT Installed
Save Changes
PURGE FROM
PANEL
Is Equipment
multi-stage
Stage
Is Equipment
HP
All Zones
Complete
HC
HC
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
Save Changes
Discard Changes
HP
HP
ZonesTime
Thermostat
Note: HP indicates Heat Pump and HC indicates Heat/Cool (Conventional).
12 English