Installation Manual

INSTALLER CHECKOUT
Installer checkout is entered by holding the and buttons for 7 seconds
continuously. Upon entering installer checkout all outputs will turn off and
thermostat inputs will be ignored. The SYSTEM CHECKOUT message will be
displayed for 2 seconds and then transition to the first step of installer checkout
as shown in the diagram on this page.
In installer checkout, the zone panel can only step forward through the test steps
so the BACK button will have effect.
The NEXT
button will navigate
to the next step.
Minimum on time: The minimum
on and off times for heating and
cooling apply to installer test. The
Time Delay Override button can
be used to speed up the minimum
on and off timers.
Timeout: If no button is pressed
installer checkout will transition to
the next step once the associated
timeout for that step has expired.
System Checkout
Display for 2 seconds
STAGE1 HEAT ON
DAT##F
STAGE1 COOL ON
DAT##F
STAGE2 HEAT ON
DAT##F
AUX1 HEAT ON
DAT##F
AUX2 HEAT ON
DAT##F
and Held
for 7 Seconds
Transition to
Home Screen
Second Stage
Installed
NEXT button pressed or
5minute timeout
DAMPER1 CLOSED
NEXT button pressed or
5minute timeout
DAMPER2 CLOSED
NEXT button pressed or
1minute timeout
DAMPER3 CLOSED
NEXT button pressed or
1minute timeout
DAMPER4 CLOSED
NEXT button pressed or
1minute timeout
OUTDOOR SENSOR READS##F
Outdoor Sensor
Installed
NEXT button pressed or
1minute timeout
INSTALLER TEST COMPLETE
Display for 2 seconds
NEXT button pressed or
1minute timeout
NEXT button pressed or
5minute timeout
NEXT button pressed or
5minute timeout
FAN ON
NEXT button pressed or
5minute timeout
NEXT button pressed or
5minute timeout
STAGE2 COOL ON
DAT##F
NEXT button pressed or
5minute timeout
Second Stage
Installed
Aux1 Installed
Aux2 Installed
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
NOTE: A minimum off time may
be enforced and an EQUIPMENT
WAIT message displayed.
No
No
No
No
No
18 English