Installation Manual

LCD HOME SCREEN DISPLAY & DESCRIPTIONS
The LCD will display the zone panel status during normal operation. The table below shows the available messages and a corresponding description.
TABLE 2 – LCD HOME SCREEN
Message Type Display Context Message Text
Normal Operation
The outdoor temperature will be displayed if OUTDOOR SENSOR is set to YES.
OUTDOOR SENSOR
<value>F
The discharge air temperature will be displayed if DAT SENSOR is set to YES.
DAT SENSOR
<value>F
Vacation mode is enabled with the Vacation button.
VACATION ENABLED
ZONE1 CONTROLS
Emergency Heat mode is enabled at the zone panel with the EM Heat button.
EMERGENCY HEAT
ENABLED
Error
Wired outdoor sensor failure (open or short).
CHECK WIRED
OUTDOOR SENSOR
Wireless outdoor sensor failure.
CHECK WIRELESS
OUTDOOR SENSOR
Discharge air temperature sensor failure (open or short).
CHECK DISCHARGE
AIR TEMP SENSOR
The thermostat inputs are not a recognized combination.
CHECK ZONE#
THERMOSTAT
Equipment Status
HVAC equipment output held off by minimum off timers. EQUIPMENT WAIT
FAN ON is only displayed when there is a continuous fan call to the HVAC equipment, and that call
is caused by a continuous fan call (G only) from one or more thermostats.
FAN ON
Equipment Type Aux Heat Type Active Stage Message Text
Heat/Cool N/A
1 STAGE 1
2 STAGE 1 AND 2
Heat Pump
Don’t care
1 Compressor COMPRESSOR 1
2 Compressor
COMPRESSOR
1 AND 2
Electric
1 Auxiliary ELECTRIC HEAT 1
2 Auxiliary ELECTRIC HEAT 2
Gas
1 Auxiliary AUX HEAT 1
2 Auxiliary AUX HEAT 2
Discharge Air
Temperature
Sensor Limits
Discharge high temperature limit exceeded and has not recovered 10°F below the limit.
DISCHARGE HIGH
TEMP EXCEEDED
Equipment has staged down based on the high temperature limit.
DOWNSTAGED ON
HIGH TEMP LIMIT
Discharge low temperature limit exceeded and has not recovered 10°F below the limit.
DISCHARGE LOW
TEMP EXCEEDED
Equipment has staged down based on the low temperature limit.
DOWNSTAGED ON
LOW TEMP LIMIT
Purge Damper purge is active.
PURGE ACTIVE
Idle No other message is being displayed.
IDLE
Time Delay
Override
Time Delay Override is active.
TIME DELAY
OVERRIDE ACTIVE
Wireless ODT
Pairing
Pairing of wireless ODT is active.
PAIRING WIRELESS
OUTDOOR SENSOR
Pairing of wireless ODT is successful.
WIRELESS OUTDOOR
SENSOR PAIRED
English 17