Installation Manual
INSTALLER SETUP
HOW TO CONFIGURE
• Press the BACK
and NEXT buttons for 7 seconds continuously.
• The message INSTALLER SETUP ENABLED will be displayed for 2
seconds and then transition to the first system setting.
• Use the or buttons to select HVAC, STAGING, or DAT (Discharge
Air Temperature) LIMITS setup, then press NEXT to enter the setup
menu. Selecting EXIT and then pressing NEXT will save installer
settings and exit the installer setup.
• Within each sub-menu use the
or buttons to adjust the setting.
• The NEXT
button will accept the current setting and navigate to the
next setting unless the last sub-menu setting is displayed. If the last sub-
menu setting is displayed, pressing NEXT will return to the main menu.
NOTE: If no buttons are pressed for 60 seconds during the installer setup.
The installer setup will exit automatically and save any changes.
The flow chart below shows the steps of the installer setup. Default
settings are show in bold. For more detailed information about each of
the system settings, refer to TABLE 1 on the following page.
OUTDOOR SENSOR
YES NO
HIGH BALANCE POINT
OFF 0°F–85°F(Steps of 5°F/65°F)
DAT SENSOR
YES NO
DAT LOW LIMIT
30°F–45°F (2.5°F steps/40°F)
DAT HIGH LIMIT
110°F–170°F (5°F steps/160°F)
DOWNSTAGE ON DAT
YES NO
SETUP COMPLETE
LOW BALANCE POINT
OFF 0°F–60°F (Steps of 5°F/20°F)
(Limited by HBP)
EQUIPMENT TYPE
HTPUMP HEAT/COOL
STAGING BASED ON
ZONES TIME TSTAT
COOLING STAGES
1 2
COMPRESSOR STAGES
1 2
HEATING STAGES
1 2
AUX HEAT STAGES
1 2
HEAT EQUIPMENT
GAS ELECTRIC
AUX HEAT
GAS ELECTRIC
Return to
Home Screen
HEAT/COOL OR
HTPUMP
ODT Installed
DAT Installed
ZONE# WEIGHTING
1 2 3
Is
Equipment HEAT
PUMP
STAGE TIME AUX
10-120 MINUTES
(by 10/default 20)
All Zones
Complete
ZONES TO STAGE
1-12 (by 1/default 2)
TIME TO STAGE
10-120 MINUTES
(by 10/default 20)
Stage
ZonesTime
Thermostat
THERMOSTAT TYPE
HEAT PUMP HEAT/COOL
FAN CTL IN PURGE
HVAC ZONE PANEL
PURGE TIME
2 3 4 5
PURGE FROM
ZONE PANEL
STAGING
HVAC
SETUP
HVAC DAT
EXIT
HTPUMPHEAT/COOL
Yes
Yes
Yes
No
A
No
No
INSTALLER SETUP
ENABLED
and Held
for 7 Seconds
A
SETUP
HVAC STAGING DAT LIMITS EXIT
NOTE: Staging is only displayed if
the equipment is multistage.
Yes
No
English 13