User Guide

MODEL 8052 TEMP SENSOR
90-2087
FIGURE 10 – DISCHARGE AIR TEMPERATURE SENSOR
DISCHARGE AIR TEMPERATURE SENSOR (INCLUDED)
Wire the discharge air temperature sensor
Model 8052 to the “DAT” terminals as
shown. See FIGURE 10.
Maximum distance of the sensor from the
zone panel is 300 feet.
Do not wire along 120VAC lines.
Refer to FIGURE 5 on page 5 for the proper
mounting location of the discharge air
temperature sensor.
THERMOSTAT TERMINAL DEFINITIONS
R – 24VAC power to thermostat
C – 24VAC power to thermostat
W – Auxiliary heat
Y – Compressor
G – Fan
O – Reversing valve
L – Fault indicator to thermostat
NOTE:
Heat pump thermostats must be used for all zones.
HEAT PUMP
HVAC TERMINAL DEFINITIONS
Y1 – First stage compressor
W1 – First stage auxiliary heat
G – Fan
O – Reversing valve (cooling)
R
W1
Y1
HEAT PUMP
O
L
C
G
RC
W
Y
O
L
C
G
RH
B
HVAC
NOTE:
REMOVE JUMPER
JMP
TO ISOLATE
TRANSFORMERS IN
MULTI-TRANSFORMER
SYSTEMS.
JMP
90-2113
FIGURE 11 – HEAT PUMP
HVAC TERMINAL DEFINITIONS
RH – 24VAC from auxiliary heat equipment
RC – 24VAC from heat pump
W – Auxiliary heat
Y – Compressor
G – Fan
O – Reversing valve
B – Reversing valve
L – Heat pump fault input
C – Common from heat pump (only needed if L is connected)
NOTE:
For two transformer systems, remove the jumper next to the RH and RC
terminals labeled JMP.
English 9