Install Instructions

TABLE 5: ZONE SYSTEM SETTINGS
System Setting Description
Factory Default Settings (bold)
and Settings Range
Number of Zones Number of zones detected.
1
2
3
Staging Based On Staging based on Zones.
Zone
Number of Zones
Zones to Stage
Selects how many Zones are required to stage up. Note: Only option if ZONES is
enabled.
2
1-9
Zone 1 Weighting The amount of precedence each zone has.
1
2
3
Zone 2 Weighting The amount of precedence each zone has.
1
2
3
Zone 3 Weighting The amount of precedence each zone has.
1
2
3
DAT Sensor Enables or disables the DAT sensor.
Yes
No
DAT Low Limit
Low Temperature Limit. Safety limit at which the HVAC equipment will turn off.
Note: Only option if DAT Sensor is enabled.
30°F to 45°F
(2.5°F steps / 35°F)
DAT High Limit
High Temperature Limit. Safety limit at which the HVAC equipment will turn off.
Note: Only option if DAT Sensor is enabled.
110°F to 170°F
(5°F steps / 160°F)
Downstage on DAT
Allows panel to downstage multistage equipment when DAT temperature comes
within 5°F high or low limit. Note: Only option if DAT Sensor is enabled.
Yes
No
18