TABLE 4: THERMOSTAT SYSTEM SETTINGS
System Setting Description
Factory Default Settings (bold)
and Settings Range
RH Sensor Offset Zone 1 Field adjustment of internal RH sensor.
0
-5 to 5
Temp Sensor Offset Zone 2 Field adjustment of controlling temperature sensors.
0°F (0°C)
-4 to 4°F (-2 to +2°C)
RH Sensor Offset Zone 2 Field adjustment of internal RH sensor.
0
-5 to 5
Temp Sensor Offset Zone 3 Field adjustment of controlling temperature sensors.
0°F (0°C)
-4 to 4°F (-2 to +2°C)
RH Sensor Offset Zone 3 Field adjustment of internal RH sensor.
0
-5 to 5
Equipment Minimum On Time Minimum on time for heating and cooling.
2 Minutes
1 to 5 Minutes
Heating Minimum Off Time Minimum off time for heating.
2 Minutes
1 to 5 Minutes
Compressor Minimum Off Time Minimum off time for compressor protection.
5 Minutes
1 to 5 Minutes
Outdoor Temperature High Balance Point Enable or disable high balance point. (Available if ODT is installed.)
Enabled
Disabled
Select Temperature
If outside temperature is above the high balance point, the aux heat operation is
not allowed. (Available if high balance point is enabled.)
65°F (14.5°C)
0 to 80°F (-18 to 22°C)
Outdoor Temperature Low Balance Point Enable or disable low balance point. (Available if ODT is installed.)
Enabled
Disabled
Select Temperature
If outside temperature is below the low balance point, the compressor operation
is not allowed. (Available if low balance point is enabled.)
20°F (-8°C)
0 to 60°F (-18 to 12°C)
Stage Rate Accumulation of equipment run time in staging determination.
Enabled
Disabled
Factor
1 = more rapid staging of equipment (comfort).
5 = slower staging of equipment (economy).
2
1 to 5
First Stage Differential First stage differential.
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
Second Stage Differential Second stage differential.
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
Third Stage Differential Third stage differential.
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
Forth Stage Differential Fourth stage differential.
1°F (0.5°C)
1 to 9°F (0.5 to 4.5°C)
Service HVAC Reminder The period for displaying the HVAC Service reminder message.
Disabled
Enabled
Recurrence Select number of months for displaying reminder.
12 Months
1 to 12 Months