Install Instructions

OUTDOOR TEMPERATURE SENSOR (INCLUDED)
Wire the outdoor temperature sensor Model
8052 to the “ODT” terminals as shown. See
FIGURE 10.
Maximum distance of the ODT sensor from
the 6000 Series is 300 feet.
Do not wire along 120VAC lines.
Outdoor temperature sensor should be
mounted:
On side of building out of direct sunlight.
Above snow line.
At least 3 feet away from exhaust vents
and condensing lines.
MODEL 8052 TEMP SENSOR
MODEL 8057 TEMP SENSOR
90-2088
90-2427
FIGURE 10 – OUTDOOR TEMPERATURE SENSOR
FIGURE 11 – DISCHARGE AIR TEMPERATURE SENSOR
MODEL 8052 TEMP SENSOR
90-2416
FIGURE 12 – RETURN AIR TEMPERATURE SENSOR
DISCHARGE AIR TEMPERATURE SENSOR (INCLUDED)
Wire the discharge air temperature sensor
Model 8057 to the “DAT” terminals as
shown. See FIGURE 11.
Maximum distance of the DAT sensor from
the 6000 Series Hub is 300 feet.
Do not wire along 120VAC lines.
Refer to FIGURE 2 on page 7 for the proper
mounting location of the discharge air
temperature sensor.
RETURN AIR TEMPERATURE SENSOR (OPTIONAL)
Wire the return air temperature sensor
Model 8052 to the “RAT” terminals as
shown. See FIGURE 12.
Maximum distance of the RAT sensor from
the 6000 Series Hub is 300 feet.
Do not wire along 120VAC lines.
Mount the sensor according to the
installation instructions provided with the
sensor.