Troubleshooting Guide

14 | Page
Measured Outlet Temperature = 115°F
Measured Outlet %RH = 12%
Outlet Air Moisture Content (Graph 2) = 0.72 ppd/CFM
Dehumidifier Capacity = (Inlet Air Moisture Content Outlet Air Moisture Content) * Airflow
(1.31 ppd/CFM 0.72 ppd/CFM)*120 CFM = 70ppd
14. Compare the capacity to the approximate performance in the table below. Performance should
be within about 20% of the capacity listed below due to the estimation of airflow through the
unit:
1830 Capacity
Inlet Air RH
Inlet Air Temperature (°F)
60
65
70
80
60%
40 ppd
50 ppd
57 ppd
70 ppd
1850 Capacity
Inlet Air RH
Inlet Air Temperature (°F)
60
65
70
80
60%
53 ppd
61 ppd
73 ppd
95 ppd
1870 Capacity
Inlet Air RH
Inlet Air Temperature (°F)
60
65
70
80
60%
62 ppd
74 ppd
98 ppd
130 ppd