Sequence of Operation
The dehumidifier will automatically “sample”
the air by turning on its blower (and the HVAC
blower if this option has been wired – see
Figure 3), and measuring the relative humidity
(RH) once every hour. Sampling will also occur
when the RH setting is lowered using the UP or
DOWN buttons on the control.
During sampling, if the RH of the air is above
the setting the dehumidifier, the compressor
will turn on. The compressor, dehumidifier
blower and HVAC system blower (if on) turns
off when the RH of the air is 3% RH below the
setting.