Install Instructions

SPECIFICATIONS
Model 1870 & 1870W
Weight 113 lbs�
Capacity (80°F, 60% RH Conditions) 130 pints per day @ 310 CFM
Power (115 VAC, Single Phase, 60Hz) 8�3 Amps operating current
Dehumidifier Inlet Air Conditions
Dehumidification: 50°F – 104°F, 40°F dew point minimum
Ventilation: 40°F – 140°F, 0% RH – 99% RH (non-condensing)
Filter MERV 8, washable
Airflow
External Static Pressure ("w.c.) Airflow (CFM)
0�0 310
0�2 270
0�4 225
0�6 175
0.6" w.c. is maximum design external static pressure.
The dehumidifier is not designed to prevent window condensation in winter� Indoor humidity levels must typically get lower than what dehumidifiers
can achieve to address window condensation� Use ventilation to lower indoor humidity levels in winter
SET UP DEHUMIDIFIER FOR INSTALLATION
IMPORTANT Cut the strap securing the compressor shipping
support bracket and remove the strap and shipping bracket�
SeeFIGURE1
CLIP OFF
PLASTIC
STRAP
REMOVE SCREWS (2)
DISCARD SHIPPING BRACKET
REINSTALL SCREWS (2)
90-2013
FIGURE 1 – REMOVE SHIPPING BRACKET
English 3