Install Instructions

MODEL 76 – CRAWL SPACE CONTROL AND WIRING
NOTE: Use 18-22 AWG wire for control wiring.
Used as a crawl space control (or remote control),
the Model 76 is mounted in the living space while
the dehumidifier is located in the crawl space.
When the dehumidifier is powered, the display on
the dehumidifier control will show “REMOTE” to
indicate that a remote control is being used. The
RH shown on the Model 76 is the RH measured at
the dehumidifier.
NOTE: Air Cycling is not an option when using a
Model 76 as a remote control.
+ -ABODT
SensorRemote
Gh Rf Cf Gs YW
HVAC EQUIP.
DH
DH
R/+
C/-
B
A
MODEL 76 CONTROL
FIGURE 7 – Model 76 Crawl Space/Sealed Attic (Remote) Wiring
90-1860
AIR CYCLING
The dehumidifier has an optional ventilation feature that can be used to circulate air through the dehumidifier, to promote uniform humidity
levels throughout the space. When this feature is enabled, the dehumidifier fan can be set to run from 0 minutes (no air cycling) to 60 minutes
(continuous) per hour. See VENTILATION / AIR CYCLING in the SYSTEM SET-UP, CHECK & START-UP section on page 7.
NOTE: The on-board control must be used when Air Cycling.
5