Install Instructions
CLIP OFF
PLASTIC
STRAP
REMOVE SHIPPING BRACKET
FIGURE 1 – Remove Shipping Bracket
90-2302
IMPORTANT: Cut the strap securing the compressor
shipping support bracket and remove the strap and shipping bracket.
See Figure 1.
SET UP DEHUMIDIFIER FOR INSTALLATION
SPECIFICATIONS
Model 1820
Weight
56 lbs.
Capacity: AHAM DH-1-2008 80°F, 60% RH Conditions 70 pints per day @ 200 CFM
Power: 115 VAC, Single Phase, 60Hz 5.8 Amps operating current
Dehumidifier Inlet Air Conditions
Dehumidification: 50°F – 104°F, 40°F dew point minimum
Ventilation: 40°F – 140°F, 0%RH – 99%RH (non-condensing)
Filter
MERV 8, washable
Airflow
200 CFM
1. Dehumidifier
2. Inlet/Outlet Collars
3. Literature
a. Installation Instructions
b. Owner’s Manual
4. Parts Bag
a. #10 x 1/2 Screws (9)
b. Threaded Barbed Fitting for Drain
Connections
c. Torx Bit
5. 10 foot, 3/4” Drain Tube
PACKAGING CONTENT
Use the screws in the parts bag to attach the duct
collars to the inlet and outlet of the dehumidifier.
See Figure 2.
OUTLET
DUCT
COLLAR
INLET
DUCT
COLLAR
FIGURE 2 – Install Duct Collars
90-2308
DUCT COLLARS
2