Specifications

What it Looks Like
APRILAIRE DEHUMIDIFICATION REPORT
Indoor Conditions at Max Latent Load
Dry Bulb Temperature 72 °F
Relative humidity 75 % RH
Desired Conditions at Max Latent Load
Dry Bulb Temperature 76 °F
Relative Humidity 55 % RH
Building Design Data
Floor Area 8000 FT2
Ceiling Height 10 FT2
Air Changes/Hour 5 ACH
CAPACITY REQUIRED 6.41 lb/hr (147.6 ppd)
Volume of Space 80000 cu ft
Volume of air needed to treat 667 cfm
Beginning Humidity Ratio .0126 lbw/lba
Beginning Dry Bulb Temperature 72 °F
Beginning Enthalpy 31.03 btu/lba
Desired Dry Bulb Temperature 76 °F
Lvg Evap Dew Point Temperature 58.7
Lvg Evap DB/WB Temperature 58.7
Lvg Evap Enthalpy 25.52 btu/lba
Total Capacity 16530 btu/hr
Sensible Capacity 9804 btu/hr
Latent Capacity 6726 btu/hr
Water Removal 6.41 lb/hr (147.6 ppd)