Specifications
Model 1160 and 1180 Control
• Modulating Control
-Demand signal is sent from a modulating humidistat to the
humidifier, which then produces a proportional output
~if no signal is sent (0 VDC), no output is produced
~if a 5 VDC signal is sent, humidifier operates at 50% of capacity
~if a 10 VDC signal is sent, humidifier will run at 100% capacity
-Humidifier’s electric heaters respond to the demand by cycling on
and off at a corresponding rate to the demand signal
-Humidity level is controlled within 3% of set points