Installation guide
  7800 Series Keypad Installation Guide  5
Wiring the 333 Suppressor
One Model 333 Suppressor is 
included with the 7873 keypad. If 
the device being controlled by the 
relay is connected to the N/O and 
C wires, install the suppressor on 
the N/O and C wires. If the device is 
connected to the N/C and C wires, 
install the 333 on N/C and C wires. 
Refer to Figure 7.
Door Strike Relay Operation
As soon as the user code sent 
from the reader is veried by the 
panel, the keypad door strike relay 
activates for 5 seconds. During this 
time, the access door connected 
to Zone 2 must be opened to start 
the programmed entry/exit timer 
and zone Bypass (Soft-Shunt™) if 
programmed and used.
Note: The 5-second door strike is panel programmable when the keypad is used on an 
XR100/XR500 or XR150/XR350/XR550 Series panel. Refer to the panel programming 
guide as needed.
Zone 2 Door Contact with Bypass (Soft-Shunt)
If the door being released by the 7873 keypad is protected, you can provide a 
programmed bypass time by connecting its contact to Zone 2 (White/Red pair) on the 
keypad and enabling the Bypass feature. See ZONE 2 BYPASS later in this document. 
Door contacts may be N/C or N/O.
Zone 3 Request to Exit
You can also connect a N/O PIR (or other motion sensing device) or a mechanical 
switch to Zone 3 (White/Orange pair) on the 7873 keypad to provide request to exit 
capability. See ZONE 3 EXIT later in this document. When Zone 3 shorts, the keypad 
relay activates for between 5 and 250 seconds. This REX time is programmable with a 
default of 5 seconds. See ZONE 3 REX STRIKE TIME later in this document. 
During this time, the user can open the protected door to start the programmed 
Bypass entry/exit timer. If the door is not opened within 5 seconds, the relay restores 
to its locked state.
Note: A Zone 3 Request to Exit is inhibited for 3 seconds after the keypad reads a card 
and a door strike occurs. This is to allow area entry and pass under a REX PIR.
Keypad Backlighting
The touchscreen illuminates at the maximum brightness any time the display is 
pressed. During an alarm condition, the touchscreen turns Red. When all alarm 
conditions are cleared from the display, the keyboard, logo, and the user-selected 
brightness is restored.
AC Power/Armed LED Operation
The LED indicates the Power and Armed status of the panel. Depending on the 
operation, the LED displays in Red or Blue as listed in the table.
1K EOL
1K EOL
1K EOL
1K EOL
Green/White – 
Connect Reader 
Data 0
White – Connect 
Reader Data 1
Orange – N/O
Gray – Common
Violet – N/C
Yellow/White
White/Yellow
Orange White
White/Orange
Red/White
White/Red
Brown/White
White/Brown
Black – Ground 
Green – Receive Data
Yellow – Send Data 
Red – Keypad Power 
– Zone 4
– Zone 3
– Zone 2
– Zone 1
All Keypads
Zones 1 to 4
7800 Series Keypads
Model 333
Supressor 
Common
–+
Magnetic Door Lock
DMP 505-12 
Power Supply
Normally 
Open
Normally
Closed
Surface and Backbox
Mounting Holes
Keypad Back
Figure 7: 5-wire Harness/Suppressor Installation