  7800 Series Keypad Installation Guide  19
Wiring Specications for Keypad Bus
When planning a keypad bus installation, keep in mind the following specications:
1.  DMP  recommends  using  18  or  22-gauge  unshielded  wire  for  all  keypad  and  
LX-Bus circuits. Do Not use twisted pair or shielded wire for LX-Bus and keypad 
bus data circuits. To  maintain  auxiliary  power integrity when using 22-gauge 
wire with a Model 7872 or 7873 do not exceed 225 feet. When using 18-gauge 
wire do not exceed 500 feet. Install an additional power supply to increase the 
wire length or add devices.
2. Maximum distance for any one circuit (length of wire) is 2,500 feet regardless 
of the wire gauge. This distance can be in the form of one long wire run or 
multiple  branches  with  all  wiring  totaling  no  more  than  2,500  feet. As  wire 
distance from the panel increases, DC voltage on the wire decreases.
3.  Maximum number of devices per 2,500 feet circuit is 40.
Note: Each panel allows a specic number of supervised keypads. Add 
additional keypads in the unsupervised mode. Refer to the panel installation 
guide for the specic number of supervised keypads allowed.
4. Maximum voltage drop between the panel (or auxiliary power supply) and any 
device is 2.0 VDC. If the voltage at any device is less than the required level, 
add an auxiliary power supply at the end of the circuit. When voltage is too low, 
the devices cannot operate properly.
Refer to the LX-Bus/Keypad Bus Wiring Application Note (LT-2031) for more 
information. Also see the 710 Module Installation Sheet (LT-0310).
Keypad Specications
MODEL NORMAL/ 
STANDBY 
CURRENT
ALARM 
CURRENT
FOUR 
ZONES
INTERNAL 
PROX 
READER
WIEGAND 
INPUT
INTERNAL 
DOOR 
STRIKE 
RELAY
7872
145mA + 1.6mA  
per active zone
215mA + 2mA  
per active zone
X X
7873
143mA + 1.6mA  
per active zone
243mA + 2mA  
per active zone
X X X X