Specifications
HarmonicGuard
®
Passive Installation
10 HGP IOM Manual - Rev. D
Provisional 600V CP and KP Kit Fuse Table
The fuse tables provided below list the branch circuit current and a recommended fuse rating that will
offer a reasonable level of protection of the branch circuit. The fuses specified in the provisional fuse
table are dependent upon any other components used in conjunction with the HGP kit such as a
customer supplied contactor or power distribution block. The intent of the provisional fuse table is to
provide the minimum sizing option for the wiring that can be used. Refer to the fuse requirements for
the selected contactor and power distribution block provided by the contactor and power distribution
block manufacturer for specific fusing required for your application.
Table 2 – Provisional Fuse Specifications for HGP 600 Volt Models
HP
kVar
Branch Current Amps
Branch Circuit
Fuse
15
5
6.8
10
30
10
13.7
20
40
15
20.5
25
50
15
20.5
25
60
20
27.4
35
75
25
34.2
40
100
30
41.0
50
125
40
54.7
70
150
45
61.6
80
200
60
82.1
100
250
75
103.0
125
300
90
123
150
350
105
144
175
400
120
164
200
450
135
185
225
500
150
205
250
600
180
246
300
700
210
287
300
800
240
328
350
900
270
369
400