6.3 Dimensions and performance, K9
Applied Thermal Control K910003
High Precision Recirculating Chiller
Feature
K910003
Dimensions L x W x H
775 x 510 x 853 mm
Cooling capacity (water @ 20
o
C)
8.5 kW (Max ambient 24C)
Temperature controller
3 term P.I.D digital
Temperature adjustable
1
o
C increments
Temperature stability
+/- 0.1
o
C
Temperature range
+4 to +35
o
C
Digital temperature display
Standard
Temperature alarm - Standard offset
10
o
C
Adjustable, High / Low
Auto diagnostic functions
Controller and sensor
Low Water Level Alarm
Optional
System volume
10 litres
Pressure control system
Standard - user adjustable
Compatible fluids
Hexid fluids / water / propylene glycol
Fluid connections
6.5, 9 & 12mm id hose tails & 3/4” BSP
male
Pump P10
10 litres per minute up to 150 psi (10 bar)
Compressor over - load protection
Standard
Emergency Off (EMO)
Via main circuit breaker (MCB)
Tool-less access
Yes
Weight
125kg
Wheels for mobility
Standard (2 locking)
Power requirements
10 amps 208 VAC, 3ph, 50/60Hz
16 amps 208VAC, 3ph, 60Hz
Condenser
Air Cooled