Instruction manual

K4, K6, K9 series chillers Installation and Operation manual
Issue 10.33
Page 21
6.3 Dimensions and performance, K9
Applied Thermal Control K910003
High Precision Recirculating Chiller
Feature
K910003
Dimensions L x W x H
775 x 510 x 853 mm
Cooling capacity (water @ 20
o
C)
8.5 kW (Max ambient 24C)
Temperature controller
3 term P.I.D digital
Temperature adjustable
1
o
C increments
Temperature stability
+/- 0.1
o
C
Temperature range
+4 to +35
o
C
Digital temperature display
Standard
Temperature alarm - Standard offset
10
o
C
Adjustable, High / Low
Auto diagnostic functions
Controller and sensor
Low Water Level Alarm
Optional
System volume
10 litres
Pressure control system
Standard - user adjustable
Compatible fluids
Hexid fluids / water / propylene glycol
Fluid connections
6.5, 9 & 12mm id hose tails & 3/4” BSP
male
Pump P10
10 litres per minute up to 150 psi (10 bar)
Compressor over - load protection
Standard
Emergency Off (EMO)
Via main circuit breaker (MCB)
Tool-less access
Yes
Weight
125kg
Wheels for mobility
Standard (2 locking)
Power requirements
10 amps 208 VAC, 3ph, 50/60Hz
16 amps 208VAC, 3ph, 60Hz
Condenser
Air Cooled