Page 20
6.2 Dimensions and performance, K6
APPLIED THERMAL CONTROL K6
High precision recirculating chiller
Feature
K6
Dimensions L x W x H
775 x 510 x 853 mm
Cooling capacity (fluid @ 17°C)
6000 watts
Microprocessor-based temperature controller
3 term P.I.D digital
Temperature adjustable
1°C increments
Temperature stability
+/- 0.1 C
Temperature range
+4 to +35C
Extended temperature range - Optional
-30 to +90C
Digital temperature display
Standard
Temperature alarm - Standard off-set +/- 10°C
Adjustable High / Low
Low fluid level alarm
Standard Visual with pump interlock
Auto diagnostic functions
Controller and sensor
System volume
7 litres
Pressure control system
Standard fitment internal - user adjustable
Compatible fluids
Hexid fluids / water / propylene glycol
Fluid connections
12mm i.d. hose tails & 3/4” BSP male
Pump P5
5 Litres per minute up to max. pressure of
150 psi (10 bar)
Pump P10
Pump P17
10 Litres per minute, up to 150 psi (10 bar)
17 Litres per minute, up to 150 psi (10 bar)
Compressor over - load protection
Standard
Emergency Off (EMO)
Via main circuit breaker (MCB)
Tool-less access
No
Weight
125kg
Wheels for mobility
Standard (2 locking)
Power requirements
10 Amps 208-230VAC 1ph 50 Hz or
5 Amps 380-415VAC 3ph 50/60Hz
Warranty
2 years parts one year labour.
Computer interface optional
RS 485 serial to modbus standard
Water cooled condenser
Optional