Page 19
6.0 Dimensions and performance, K series
6.1 Dimensions and performance, K4
APPLIED THERMAL CONTROL K4
High precision recirculating chiller
Feature
K4
Dimensions L x W x H
775 x 510 x 853 mm
Cooling capacity (fluid @ 17°C)
4500 watts
Microprocessor-based temperature controller
3 term P.I.D digital
Temperature adjustable
1°C increments
Temperature stability
+/- 0.1 C
Temperature range
+4 to +35C
Extended temperature range - Optional
-30 to +90C
Digital temperature display
Standard
Temperature alarm - Standard off-set +/- 10°C
Adjustable High / Low
Low fluid level alarm Option
Visual
Low flow alarm option
Visual
Auto diagnostic functions
Controller and sensor
System volume
7 litres
Pressure control system
Standard fitment internal - user adjustable
Compatible fluids
Hexid fluids / water / propylene glycol
Fluid connections
12mm i.d. hose tails & 3/4” BSP male
Pump P5
5 Litres per minute up to max. pressure of
150 psi (10 bar)
Pump P10
Pump P17
10 Litres per minute, up to 150 psi (10 bar)
17 Litres per minute, up to 150 psi (10 bar)
Weight
125kg
Wheels for mobility
Standard (2 locking)
Power requirements
13 Amps 210-230VAC 1ph 50 Hz
Warranty
2 years parts one year labour.
Computer interface optional
RS 485 serial to modbus standard
Water cooled condenser
Optional