CAL controller error messages
Message displayed Cause and correction
InPt FAiL
Sensor has failed.
Order replacement part number EA-038
Data FAiL
Controller problem.
Switch off, then on.
If problem is persistent, order replacement
part EA-055
- AL - (At start up)
Ambient temperature outside of permitted
range, 5°C - 40°C
- AL - (After changing setpoint)
Restart the controller to reset the alarm
- AL - (During normal operation)
Fault on system.
Refer to Troubleshooting, section 4.1
Fluid flow and pressure
K series chillers contain a high pressure volumetric pump capable of 150 psi. All units are
supplied with a pre-set maximum of 50 psi. Pressures above this will cause the internal
safety bypass valve to open, protecting your application from potentially dangerous
pressures.
It is possible for customers to change the operating pressure of the chiller, as follows:
1. Remove the cover from the chiller, giving access to the top compartment, figure 1.
2. With the chiller running, release the locking nut on the pressure relief valve.
3. Turn the valve knob anticlockwise to reduce the flow/pressure, clockwise to
increase the flow/pressure.
4. The pressure can be observed on the gauge on the front panel.
Caution:
Changing the flow/pressure with the pressure relief valve will also change the preset
pressure safety setpoint. This will move to a lower pressure than the factory setting when
decreasing the flow/pressure, and to a higher pressure when increasing the flow/pressure.