6.2 Specifications
Environmental
· For indoor use only
· Altitude: up to 2000 metres
· Ambient temperature range: 4°C - 40°C
· Maximum relative humidity: 80% for ambient temperatures up to 31°C, decreasing
linearly to 50% relative humidity at 40°C ambient temperature.
· Mains supply voltage not to exceed ±10% of the nominal voltage.
· Installation Category II
· Pollution Degree 2
KTR
· Cooling capacity: 480 Watts at 22°C
· Dimensions, height x width x depth: 515 x 315 x 315mm (20 x 12.4 x 12.4 inches)
· Weight: 30kg (66lbs)
· Cooling temperature range: 4°C - 30°C
· Pumps available
§ High pressure volumetric type: 2litre/minute or 3litre/minute
§ Low pressure centrifugal type: 6 litre/minute
· Fluid connections: ¼ BSP x 10mm (3/8) Nickel plated brass hose tail adaptors.
Custom connections available.
· Temperature stability: ±0.2°C, with stable load, dependent on stable ambient
temperature
· Power requirements: 3 Amps 230V 50/60Hz, 7 Amps 115V 60Hz
· Warranty: 2 years parts, 1 year labour.
KTC
· Cooling capacity: 480 Watts at 22°C
· Dimensions, height x width x depth: 515 x 315 x 315mm (20 x 12.4 x 12.4 inches)
· Weight: 30kg (66lbs)
· Cooling temperature range: 4°C - 30°C
· Pumps available
§ High pressure volumetric type: 2litre/minute or 3litre/minute
§ Low pressure centrifugal type: 6 litre/minute
· LED temperature display resolution: 1°C standard, 0.1°C option
· Fluid connections: ¼ BSP x 10mm (3/8) Nickel plated brass hose tail adaptors.
Custom connections available.
· Temperature stability: ±0.2°C with stable load, dependent on stable ambient
temperature
· Power requirements: 3 Amps 230V 50/60Hz, 7 Amps 115V 60Hz
· Warranty: 2 years parts, 1 year labour.