5.3   Troubleshooting 
Symptom Causes 
Compressor not running, 
but fan running 
Is the controller displaying an alarm? 
If there is no obvious cause, check… 
·  The condenser is clean 
·  Ambient temperature not above 30°C 
The likely cause is the compressor’s internal protection has been activated and 
should restart in five minutes. 
Noisy operation / 
High fluid pressure 
And/or low flow 
Check: 
·  No restrictions in the pipe work 
·  Pressure set too low (factory set pressure altered?) 
Clean system with weak detergent solution, rinse thoroughly to remove all 
detergent. Use Hexid fluid as coolant. 
Fluid lines becoming 
fouled brown or green 
Algae contamination. 
Clean system with weak detergent solution, rinse thoroughly to remove all 
detergent. Replace fluid lines with black lines, if not already fitted, to inhibit 
algae growth. Use Hexid fluid as coolant. 
Fluid seen leaking from 
system 
Under high humidity conditions, fluid may appear to be leaking from the 
system. This is usually just condensation, but do check for fluid leaks. 
Poor cooling 
Continued failure to cool may indicate high ambient temperature or excessive 
load applied to the unit. Check these first 
Otherwise, may be caused by blocked condenser. 
Clean with soft brush or vacuum cleaner with brush attachment 