Instruction manual
KT series chillers – Installation and Operation manual
Issue 7.0 Page 13
Caution:
Changing the flow/pressure with the pressure relief valve will also change the preset
pressure safety setpoint. This will move to a lower pressure than the factory setting when
decreasing the flow/pressure, and to a higher pressure when increasing the flow/pressure.
Caution:
When the flow/pressure is manually increased by the pressure relief valve, the safety
provided by the valve will be effected at higher pressures than standard. For this reason,
please ensure that it is safe for your application to operate at pressures in excess of 35 psi.
A blockage in your application could result in the pressure exceeding the raised safety
pressure.
We recommend that pressures exceeding 60psi must never be used.
5.2 Maintenance and service requirements
Caution: Failure to carry out service at the specified intervals may permanently damage
your equipment.
Interval Actions
Weekly Check fluid level (unless checked by Operator)
Check external connections for leaks (unless checked by Operator)
Monthly Check the condenser (air intake) is free from obstructions or accumulations of debris.
Cleaning may be achieved with a domestic vacuum cleaner with brush attachment.*
Annually Change the fluid (unless changed by Operator)
Check for fluid leaks throughout the whole system.
Check the condenser for fouling.
* Caution: Never blow the condenser out with compressed air.
i
i
i
i
Technician
section